ƒfƒ“ƒZƒCEƒ‰ƒ€ƒ_Дޮ‰ïŽÐ

Site map
Last Update 2003.06.09

DLP-SERIES

  • AC-DC DIN rail Mount
  • 75-240W
DLP-SERIES

Model name

DLP-SERIES

¡Features

  • DIN rail attachment correspondence
  • 87% of electric power conversion efficiency, high electric power density 0.21 W/cm³
  • A sag alarm lamp is equipped standardly.
  • Circumference [ operation ] temperature: -10-50Ž of 100% load use are possible.
  • An input-and-output terminal stand prepares two types of a block terminal and a cage European terminal.

¡Specifications(technical data download)

  DLP75-24-1 DLP100-24-1 DLP120-24-1 DLP180-24-1 DLP240-24-1
Rated Output Voltage 24V
Maximum Output Current 3.1A 4.1A 5A 7.5A 10A
Maximum Output Power 75W 100W 120W 180W 240W
Input Voltage Range 85 - 132VAC/170 - 264VAC (automatic change) 85 - 264VAC (universal input)
Efficiency (100/230VAC) 82%/83% 83%/85% 83%/85% 84%/87% 82%/86%
Operating ambient temperature - 10Ž - +60Ž (-10Ž - 50Ž : 100%, +60Ž : 60%)
Cooling Convection cooling
Size (W X H X D mm) 50 60 60 80 120
97
110
Safety Standard CE Marking (Low Voltage Directive), and UL60950, UL508, CSA60950, EN60950 and
EN50178 Each acquisition schedule

As for the mention contents of this page, understand beforehand because it sometimes changes.